04/23/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
Reference: Lighting Plans.
#1. Provide or show wiring methods for the new pole mounted luminaires. Shouldn't the luminaires by the streets comply with chapter 8 of the Tucson/Pima County Outdoor Lighting Code?
#2. Revise the text size (font) to a minimum of 3/32" for the luminaire schedule on plan sheet SE4.0.
#3. Ref: Plan Sheet SE3.1. It appears that some of the 'SA' luminaires are to close or over- lapping.
#4. Ref: Plan Sheet SE1.0.
(a) Note #5 states that the type 'EF' luminaires are to be removed, yet they are shown as new under the installed lumens. Also the 'EE' luminaires are shown as new. Please clarify.
(b) The quantity shown for the 'SA' luminaires does not correlate with the amounts shown on the site plans and the luminaire schedule at the bottom of this plan sheet. Please clarify.
Ref:2012 IBC 107.2.1, 2011 NEC, Tucson/Pima County Outdoor Lighting Code
04/23/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet SE5.0; Light Pole Foundation: Please provide structural calculations for the 25'-0" light pole foundation.