Review Details: COMMERCIAL - TI
Permit Number - T18CM02539
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/05/2018 | ANDREW CONNOR | ZONING | REVIEW | Approved | |
| 04/05/2018 | ACONNOR1 | ENGINEERING | REVIEW | Passed | |
| 04/09/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 04/09/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Thermostats that are new or are being relocated shall comply with the capabilities required by Section C403.2.4, IECC 2012. 2. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C302.2, C403.2.1, and C403.2.2, IECC 2012 as amended by the City of Tucson, and Section 312.1, IMC 2012. |
| 04/09/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/09/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 04/09/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | The next upstream manhole has a rim elevato that is higheer than the finished floor elevation. Provide a backwater valve. Reference: Section 715.1, IPC 2012. |
| 04/09/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 04/12/2018 | MARTIN BROWN | FIRE | REVIEW | Approved |