Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T18CM02485
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/13/2018 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/13/2018 | SSHIELD1 | ENGINEERING | REVIEW | Passed | |
| 04/13/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Coordinate the descriptions of the envelope assemblies with the architectural drawings (e.g. the exterior walls have R-21 cavity insulation but only R-5 for continuous insulation). Provide the U-value calculations for the roof (see footnote b on the COMcheck envelope assembly. [Initial comment: Revise the COMcheck envelope compliance certificate; use the correct code (2012 IECC) and coordinate the insulation with the drawings.] |
| 04/13/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/16/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Update the registrant seal expiration date. #2. Provide complete compliance with the 2012 IECC for the lighting. #3. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code. Ref: 2012 IBC sec107.2.1. |
| 04/19/2018 | BLARSON1 | FIRE | REVIEW | Needs Review |