Permit Number: T18CM02485
Parcel: 129020440

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T18CM02485
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2018 STEVE SHIELDS ZONING REVIEW Approved
04/13/2018 SSHIELD1 ENGINEERING REVIEW Passed
04/13/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Coordinate the descriptions of the envelope assemblies with the architectural drawings (e.g. the exterior walls have R-21 cavity insulation but only R-5 for continuous insulation). Provide the U-value calculations for the roof (see footnote b on the COMcheck envelope assembly. [Initial comment: Revise the COMcheck envelope compliance certificate; use the correct code (2012 IECC) and coordinate the insulation with the drawings.]
04/13/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/16/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Update the registrant seal expiration date.
#2. Provide complete compliance with the 2012 IECC for the lighting.
#3. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code.
Ref: 2012 IBC sec107.2.1.
04/19/2018 BLARSON1 FIRE REVIEW Needs Review