Review Details: COMMERCIAL - TI

Permit Number - T18CM02485
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/04/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/04/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Revise the COMcheck envelope compliance certificate; use the correct code (2012 IECC) and coordinate the insulation with the drawings.
2. Show how supply air to room 108 is to return to the AC unit.
3. Show how secondary condensate drainage is provided for the new fan coils.
04/04/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/04/2018 ROBERT SHERRY WATER REVIEW Completed
04/04/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.0; Partition Detail B: Are the new studs connected to the existing CMU wall? Please verify.
2. Sheet A1.0; Partition Detail B: The top of this partition must be braced to the existing roof structure. Please indicate the brace and give the brace size, spacing, and connection to the structure above and the the partition.
3. Sheet A1.0; Partition Detail C: The top of this partition must be braced to the existing roof structure. Please indicate the brace and give the brace size, spacing, and connection to the structure above and the the partition.
4. Sheet A2.0; South Elevation: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the key note indicators.
5. General: Please provide structural calculations for the new foundation and wall designs.
6. General: Please provide written responses to all review comments.
04/05/2018 MARTIN BROWN FIRE REVIEW Reqs Change Code review box indicates NO sprinklers. Another part of cover sheet indicates sprinklers. Please clarify.
04/11/2018 LPEREZ2 ELECTRICAL-COMMERCIAL REVIEW Needs Review
04/11/2018 LPEREZ2 ENGINEERING REVIEW Needs Review
04/11/2018 LPEREZ2 ZONING REVIEW Needs Review