Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T18CM02482
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/01/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A-1; Existing Floor Plan: Per the IBC Section 1607.14, interior walls and partitions that exceed six feet in height shall have adequate strength to resist a minimum of 5 PSF horizontal load. Please provide a detail on the drawings indicating diagonal bracing from the top of the partition wall to the existing structure above. Include the bracing size and spacing, in addition to the number and size of connectors of the bracing to the top of the partition and to the existing structure above. 2. Sheet A-1; Existing Floor Plan: On the drawings, provide details indicating all grab bars, their lengths, and their locations. Use ICC/ANSI Figure 604.5.1 and Figure 604.5.2. 3. Sheet A-2; Furniture Floor Plan: Two elevation indicators reference Sheet A4. Please revise the reference sheet to A-3. 4. Sheet A-3; Countertops Floor Plan: Two elevation indicators reference Sheet A4. Please revise the reference sheet to A-3. 5. Sheet A-4; Foundation Plan: Please indicate a detail on this sheet depicting the slab, foundation, reinforcing, and anchor bolts for the shed. 6. General: Please provide written responses to all review comments. |
| 05/02/2018 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Principle Planner PROJECT: 2618 E Fort Lowell Road T18CM02482 Building Plan (1st Review) TRANSMITTAL DATE: May 2, 2018 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Until all other PDSD review agencies have approved the building plans zoning cannot approve. Once the above comments are addressed Zoning will provide an over-the-counter review. Please call or email to schedule an appointment for this review. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 05/07/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide wattage calculations for the interior lighting to verify compliance with the 2012 IECC. Com-check or other. #2. Plan sheet A-3 shows exterior lighting not shown on the electrical lighting plan. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code. Provide lumen calcs to verify compliance with this Code. All new and existing lighting included in this parcel (Site) must be taken into consideration. See section 104 for plan and permit submittal requirements. Provide lighting area, option used, allowed lumens vs total lumens. This code can be printed or downloaded from www.tucsonaz.gov/pdsd. #3. Provide a wiring branch circuit and feeder legend or table showing the new conductor, conduit, sizes and types, or show this in the panel schedules. #4. Provide a detailed luminaire schedule that correlates with the proposed lighting to be installed. Ref: 2012 IBC sec 107.2.1, 2011 NEC, Tucson/Pima County Outdoor Lighting Code |
| 05/08/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Clarify the natural ventilation calculations; the only operable windows are located in the restroom and the workroom, which are not applicable to ventilation of the display, office, hall, and sales rooms. See also Section 402.3, IMC 2012 with regard to natural ventilation of adjoining spaces. Reference: Section 401.2, IMC 2012. |
| 05/09/2018 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 05/09/2018 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Verify the location of the existing water meter, Tucson Water data shows the meter located on the South side of the property in the utility easement. Reference: Section 107.2.5, IBC 2012. 2. Show the location of the reduced pressure backflow assembly on the drawings; indicate the size of the assembly. Reduced pressure backflow prevention assemblies are required at the water meter for multi-use commercial buildings. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf. |
| 05/09/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | . |
| 05/09/2018 | ROBERT SHERRY | WATER | REVIEW | Reqs Change | 1. Verify the location of the existing water meter, Tucson Water data shows the meter located on the South side of the property in the utility easement. Reference: Section 107.2.5, IBC 2012. 2. Show the location of the reduced pressure backflow assembly on the drawings; indicate the size of the assembly. Reduced pressure backflow prevention assemblies are required at the water meter for multi-use commercial buildings. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://www.tucsonaz.gov/files/water/docs/backflow-ordinance.pdf. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 05/15/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
| 05/15/2018 | QJONES1 | REJECT SHELF | Completed |