Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T18CM02451
Review Name: WALK THRU - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/04/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | AC units with a cooling capacity greater than or equal to 33,000 BTUH and with a SEER less than14.3 (i.e. 10% greater than the minimum SEER of 13.0) will require the addition of an economizer. Reference: Section C403.3.1 (exception 6), IECC 2012. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/05/2018 | LPEREZ2 | APPROVAL SHELF | Completed |
| 04/05/2018 | LPEREZ2 | OUT TO CUSTOMER | Completed |
| 04/05/2018 | LPEREZ2 | REJECT SHELF | Completed |