Permit Number: T18CM02427
Parcel: 13220003A

Address:
3401 E GAS RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM02427
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/30/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Arrays 1 & 2 are designated on the PV DESCRIPTION on sheet PV0.0 to be sprinklered. Verify sprinkler load is included in structural loading of canopy. IBC 1605.1
04/30/2018 GPERU1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. ELECTRICAL NOTE #22 indicates that circuit breakers and disconnect switches lugs are rated for 75 degree min., 90 degree rating on lugs is required to use this this ampacity table for sizing conductors. NEC 310.15 (3)
2. Specify the AIC rating of PV Panel and AC disconnect. NEC 110.9
3. Provide a label on electrical equipment requiring examination or maintenance of potential arc flash hazard in a clearly visible location. NEC 110.16
4. Provide professional registrant seal on sheets PV00-PV1.1
5. PV SYSTEM DESCRIPTION notes lists (6) structures; provide description of all structures or correct note. IBC 107.2.1
04/30/2018 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: 3401 E. Gas Road - Solar Covered Parking Structure
T18CM02427
Building Plan (1st Review)

TRANSMITTAL DATE: April 30, 2018

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Until DP18-0076 is approved Zoning cannot approve the building plans

3. Until all other PDSD review agencies have approved the building plans zoning cannot approve.

Once the above comments are addressed Zoning will provide an over-the-counter review. Please call or email to schedule an appointment for this review.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956

Final Status

Task End Date Reviewer's Name Type of Review Description
05/07/2018 KROBLES1 OUT TO CUSTOMER Completed