Permit Number: T18CM02394
Parcel: 105095510

Address:
4701 N STONE AV

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM02394
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2018 JVINCEN1 FIRE REVIEW Approved
04/26/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Verify that the specified sensor faucets for the public lavatories have an automatic time-out so that they will dispense a maximum of 0.25 gallons per metering cycle. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Verify that all of the vents (i.e. "VBG") rise vertically to at least 6" above the flood rims of the fixtures they protect prior to running horizontally. (Note: see the definition of "horizontal" in Section 202, IPC 2012.) Reference: Section 905.4, IPC 2012.
04/26/2018 ROBERT SHERRY WATER REVIEW Completed
04/26/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
05/01/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments, Also provide a written response.
#1. Where is the Key or legend for the numbers in the hexagon boxes? Or is this not relevant to this project. Ref: Plan Sheets, E1, E1.1, E1.2.
#2. What does "REF1-E4" refer to ? Ref: Plan Sheet RE1.1.
#3. Include the new Compressor House transformer, panels 'CHA, CHL, feeders, disconnects, conduit, conductor sizes and types in the Line Diagram. Also include in the load calcs.
#4. Per comment #1. ( numbered hexagon boxes ) it is unclear as to the scope of work proposed for the exterior building lighting. If the exterior lighting is being modified or retrofitted, then Outdoor Lighting Code compliance will be required.
#5. Please provide a narrative for the proposed electrical work to be performed for this project.
Ref; 2012 IBC 107.2.1, 2011 NEC, Tucson/Pima County Outdoor Lighting Code.
05/30/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved 1. Sheet A2; Rear Elevation 3: At overhead door 7 (near Grid 6), the elevation indicates a dock leveller at the door, while the floor plan on Sheet A1 does not indicate the leveller. Please clarify.
2. Sheet A2; Side Elevation 4: The floor plan on Sheet A1 indicates a door at Grid J, while the elevation doe not indicate a door in that location. Please clarify.
3. General: Please provide written responses to all review comments.