Permit Number: T18CM02352
Parcel: 12806072G

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM02352
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2018 JVINCEN1 FIRE REVIEW Approved
04/25/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 424.10, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
04/25/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide heating and cooling load calculations that justify the capacities of the new AC-1 for this activity. Reference: Sections C302.2, C403.2.1, and C403.2.2, IECC 2012 as amended by the City of Tucson, and Section 312.1, IMC 2012.
04/25/2018 ROBERT SHERRY WATER REVIEW Completed
04/27/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change GENERAL STRUCTURAL NOTES. IBC 107.2.1
1. Cite the correct seismic design category for the City of Tucson on the GENERAL STRUCTURAL NOTES.
2. Correct the edition of the IBC to the 2012 edition on SPECIAL INSPECTIONS. IBC 1704.1
04/27/2018 GPERU1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change #1. Provide compliance with the Tucson/Pima County Outdoor Lighting Code. If claiming exemption per section 401.2.1(3), verify full cut-off shielding.
04/30/2018 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: Jack in the Box - 1195 S. Craycoft Rd.
T18CM02352
Building Plan (1st Review)

TRANSMITTAL DATE: April 30, 2018

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Provide a note on the plan stating that all accessible route slopes are to comply with ICC A117.1, Section 403.3; 5% maximum running slopes and 2% maximum cross slopes.

3. Detail 6, sheet SD2.1 does not match what is shown on the plan.

4. Provide a copy of the approved site plan that permitted the change from angled parking to parallel parking along the north side of the site.

5. Until all other PDSD review agencies have approved the building plans zoning cannot approve.

Once the above comments are addressed Zoning will provide an over-the-counter review. Please call or email to schedule an appointment for this review.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956