Permit Number: T18CM02347
Parcel: 12310001C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM02347
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref; Plan Sheet E2.0.1. There is an arrow pointing to canopy lighting, but no luminaires are shown. Please clarify.
#2. Ref; Plan Sheet E2.0.0. Identify the landscape lighting and shielding on the lumen calcs. Also include the canopy and traffic bollards if not already. If the landscape lighting is not fully shielded, include calcs for unshielded lighting. Sec 104.2.(1).
#3. Verify compliance with section102.4.1.
#4. Provide compliance with section 104.2.1(1) (2) (3).
Ref; 2012 IBC aes 107.2.1, Tucson/Pima County Outdoor Lighting Code