Permit Number: T18CM02347
Parcel: 12310001C

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM02347
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
04/19/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Ref: Plan sheet E2.0.0
(a) Provide full compliance with the Tucson/Pima County Outdoor Lighting Code. See section 104 for plan submittal requirements. This code can be printed or downloaded from www.tucsonaz.gov/pdsd.
#2. Provide a detailed description or narrative of the scope of work proposed for this project.
#3. Provide complete panel schedules for panels associated with the proposed lighting for this project.
Ref: 2012 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code
04/20/2018 STEVE SHIELDS ZONING REVIEW Approved
04/25/2018 LOREN MAKUS ENGINEERING REVIEW Passed