| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/19/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 04/19/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Ref: Plan sheet E2.0.0 (a) Provide full compliance with the Tucson/Pima County Outdoor Lighting Code. See section 104 for plan submittal requirements. This code can be printed or downloaded from www.tucsonaz.gov/pdsd. #2. Provide a detailed description or narrative of the scope of work proposed for this project. #3. Provide complete panel schedules for panels associated with the proposed lighting for this project. Ref: 2012 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code |
| 04/20/2018 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
| 04/25/2018 | LOREN MAKUS | ENGINEERING | REVIEW | Passed |