Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T18CM02303
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/11/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 05/11/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 05/16/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Ref; Plan Sheet E103, E105. Panel WH not included in the one line diagram. Please clarify. #2. Provide load calcs for the electrical service and for the panelboards associated with this project. Ref; 2012 IBC sec 107.2.1, 2011 NEC, City of Tucson Commercial Plan Submittal Requirements. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/06/2018 | QJONES1 | APPROVAL SHELF | Completed |
| 07/06/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
| 07/06/2018 | QJONES1 | REJECT SHELF | Completed |