Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Permit Number: T18CM02298
Parcel: 13624446A

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM02298
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/23/2018 MMORENO1 ZONING REVIEW Approved
05/25/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change There appears to be several locations where the waste stack from the 2nd floor either dropping directly into a horizontal drain or having less than 10 pipe diameters separation from the connection with the horizontal drain. [Initial comment: Horizontal branches shall connect no closer than ten diameters downstream of the bases of vertical stacks. Reference: Section 704.3, IPC 2012.]
05/25/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 3; Sheet A0.2; Enlarged Plan 1: Please add a note to Key Note 25 indicating the flag pole and foundation calculations will be a deferred submittal.
2. Previous Comment 13; Sheet A4.2; Detail 8: The vertical column is described as a TS (indicating a square tube). Please revise the note to indicate a pipe column.
3. Previous Comment 18; Sheet S1.0; General Structural Notes (Foundations): One copy of the soil report was not provided as requested.
4. Previous Comment 23; Sheet S2.1; Framing Keynotes: Note 5 was not located. Please verify.
5. General: Please provide written responses to all review comments.
05/25/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
06/06/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments, Also provide a written response.
Ref: Outdoor Lighting Calculations. Plan Sheet ES101. Please revise the following information.
(a) The Option #1 used in the calcs is for LPS (low pressure sodium) lighting. For LED full cut-off should be option #2.
(b) The luminaire quantity and lumen output totals do not correlate with the site plan and the luminaire schedule. For example, the site plan shows 6- 'P2' luminaires. The lumen calcs show 3, the luminaire schedule shows them at 23,811 lumens each, the lumen calcs show them at 43,414 each. The math doesn't add up. Please revise to show the correct values.
(c) What about the existing parking lights shown on plan sheet ED101?
Ref: 2012 IBC sec 107.2.1, Tucson/Pima County Outdoor Lighting Code, 2011 NEC
06/11/2018 JOHN VAN WINKLE ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/15/2018 QJONES1 APPROVAL SHELF Completed
06/15/2018 QJONES1 OUT TO CUSTOMER Completed
06/15/2018 QJONES1 REJECT SHELF Completed