Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM02244
Parcel: 11612118D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM02244
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2018 JVINCEN1 FIRE REVIEW Approved
04/23/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Exits are not allowed to pass through kitchens or stock rooms. The occupant load exceeds 50 persons therefore a minimum of 2 exits are required. IBC 1014.2 item 4.
2. Remove reference to the California Building Code from the referenced code on GENERAL STRUCTURAL NOTES. IBC 107.2.1
3. Cite the correct seismic design category for the City of Tucson on the GENERAL STRUCTURAL NOTES.
4. Correct the edition of the IBC to the 2012 edition on SPECIAL INSPECTIONS. IBC 1704.1
04/25/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
04/25/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/25/2018 ROBERT SHERRY WATER REVIEW Completed
04/27/2018 GPERU1 ELECTRICAL-COMMERCIAL REVIEW Reqs Change #1. Provide compliance with the Tucson/Pima County Outdoor Lighting Code. If claiming exemption per section 401.2.1(3), verify full cut-off shielding.
04/30/2018 STEVE SHIELDS ZONING REVIEW Reqs Change PDSD TRANSMITTAL

FROM: Steve Shields
Principle Planner

PROJECT: Jack in the Box - 1202 W. Saint Mary's Road
T18CM02244
Building Plan (1st Review)

TRANSMITTAL DATE: April 30, 2018

1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. It appears that keynote 33 is pointing to accessible signs and should be keynote 35.

3. Provide a note on the plan stating that all accessible route slopes are to comply with ICC A117.1, Section 403.3; 5% maximum running slopes and 2% maximum cross slopes.

4. Detail 6, sheet SD2.1 does not match what is shown on the plan.

5. Until all other PDSD review agencies have approved the building plans zoning cannot approve.

Once the above comments are addressed Zoning will provide an over-the-counter review. Please call or email to schedule an appointment for this review.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956