Permit Number: T18CM02240
Parcel: 10508013A

Address:
4949 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM02240
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2018 JPEELDA1 FIRE REVIEW Approved
04/23/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. The clearance around the water closet cannot be less than 60", other fixtures are not allowed in this clear space. Mens restroom. ICC A117.1
2. Exits are not allowed to pass through kitchens or stock rooms. The occupant load exceeds 50 persons therefore a minimum of 2 exits are required. IBC 1014.2 item 4.
3. Remove reference to the California Building Code from the referenced code on GENERAL STRUCTURAL NOTES. IBC 107.2.1
4. Cite the correct seismic design category for the City of Tucson on the GENERAL STRUCTURAL NOTES.
5. Correct the edition of the IBC to the 2012 edition on SPECIAL INSPECTIONS. IBC 1704.1
04/25/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Provide heating and cooling load calculations that justify the capacities of the new AC-1 for this activity. Reference: Sections C302.2, C403.2.1, and C403.2.2, IECC 2012 as amended by the City of Tucson, and Section 312.1, IMC 2012.
04/25/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide automatic faucets for the lavatories, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for at least 10-seconds for accessibility. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
2. Verify that all three compartments of the 3-compartment sink are indirectly drained to the new floor sink and are independent of each other. Reference: Sections 801.2 and 802.1.8, IPC 2012.
3. Revise the floor drains in the kitchen area to drain through the grease interceptor. Reference: Section 1003.3 (A), IPC 2012 as amended by the City of Tucson.
04/25/2018 ROBERT SHERRY WATER REVIEW Completed
04/26/2018 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T18CM02240 - T.I. Interior remodel and Exterior Façade Makeover
Tenant Improvement Plans (1st Review) Jack In The Box - Food Service
4949 N Oracle Road - C-3 Zoning

TRANSMITTAL DATE: April 26, 2018

DUE DATE: May 2, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the building plans but cannot approve them at this time. While the proposed interior changes do not affect zoning requirements zoning cannot approve the plans until the PDSD Commercial Plan Reviewers have completed their review and approved the building plans.

2. COMMENT: On sheet SD1.0, Keynote 4 states that all striping will be repainted. However the striping behind the Accessible parking shall be removed, see redlines on sheet SD1.0

2. COMMENT: Zoning will review the building plans on the next submittal as it relates to the zoning review purview and assure that the striping as noted above has been removed.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: building plans and current or approved version of the DP as reference.
05/01/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide complete compliance with the 2012 Tucson/Pima County Outdoor Lighting Code for the exterior lighting. This Code can be printed or downloaded from www.tucsonaz.gov/pdsd. See section 104 for plan submittal requirements.