Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM02231
Parcel: 12616319D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM02231
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/13/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/13/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide calculations to show that adequate combustion air is available for the water heater. Reference: Section 304.1, IFGC 2012.
2. Show how the size of the vent for the water heater was determined, including the vent materials, the total vent height, offset dimensions, and the size of the draft hood on the appliance. Reference: Sections 503.6.9 and 504.2.2, IFGC 2012.
3. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Sections C302.2, C403.2.1, and C403.2.2, IECC 2012 as amended by the City of Tucson, and Section 312.1, IMC 2012.
4. The COMcheck Mechanical Compliance Certificate indicates that the proposed air conditioners will not have economizers but the equipment schedule calls for the units to have economizers. Clarify how the units will be equipped. Reference: Section C403.3, IECC 2012.
5. If the proposed air conditioning units are equipped with economizers, clarify how excess outside air relief from the building is to be accomplished without recirculation of the relief air. Reference: Section C403.3.1.1.4, IECC 2012.
04/13/2018 ROBERT SHERRY WATER REVIEW Completed
04/18/2018 DAVID RIVERA ZONING REVIEW Approved
04/20/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide evidence on the exterior lighting plan that the proposed exterior lighting is in full compliance with the 2012 Tucson/Pima County Outdoor Lighting Code. See section 104 for plan submittal requirements.
#2. Show full compliance with the 2012 IECC.
Ref: 2012 IBC sec 107.2.1, 2012 IECC, 2011 NEC, 2012 Tucson/Pima County Outdoor Lighting Code.
04/20/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Reqs Change 1. A minimum of 2 exit doors are required from the restaurant with panic or fire exit hardware; specify hardware type for existing exit doors. IBC 1008.1.10
2. Specify panic or fire exit hardware for new entrance door. IBC 1008.1.10
3. Provide the occupant load for the outside patio because railing is being installed that encloses the dining area. IBC 1004.5
4. Specify anchorage of new walls to roof ceiling. IBC 107.2.1
5. The occupant load from the outside patio must be added to the building occupant load. Provide total O.L. IBC 1004.5.
6. Where more than (1) dining surface is provided for ADA use they shall be distributed throughout the dining area alon an accessible route. IBC 1108.2.9.1
7. Specify the area of the out door patio area. IBC 107.2.1
8. Indicate the use of the outdoor patio area; specify if it will be used for outdoor dining. Will require 2 exits with panic hardware where the occupant load exceeds 50 persons. IBC
107.2.1, 1008.1.10
04/25/2018 LOREN MAKUS ENGINEERING REVIEW Passed