Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM02148
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/10/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
04/13/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | Verify that the pipe sizes called out for the flush valves will not result in water velocities greater than that recommended by the pipe manufacturer (e.g. limit the water velocity to less than 8 FPS for copper). At a minimum design flow rate of 25 GPM for a siphonic, flush-valve water closet, a 1" Type L copper pipe has a flow velocity of 9.7 FPS. Reference: Table 604.3, IPC 2012. |
04/13/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
04/13/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
04/18/2018 | DAVID RIVERA | ZONING | REVIEW | Approved | |
04/19/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
04/25/2018 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
04/27/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A9.0.1; Partition Types 7C and 7D (2 Hour): The boxed information indicates a one hour rated partition, while the Partition Type indicates a two hour. Please coordinate. 2. Sheet A9.0.1; Partition Type 8: The Partition Types 8A and 8C indicate non-rated, one hour, and two hour rated partitions, while the boxed information does not indicate any rated assemblies. Please clarify. 3. Sheet A9.3.0; Door Schedule: Doors 1102C, 1106B, 1107B, and 1108B are located in smoke partitions. Per Sheet G3.1 (Door Fire Resistive Construction Symbols), these doors require a fire resistance rating that is not indicated in this schedule. Please provide the rating, and reference Sheet G3.1 for more information. 4. Sheet A9.3.0; Door Schedule: Doors 1115, 1118B, and 1118C are not listed in this schedule. Per Sheet G3.1 (Door Fire Resistive Construction Symbols), these doors require a fire resistance rating that is not indicated in this schedule. Please add these doors to the schedule, provide the rating, and reference Sheet G3.1 for more information. 5. Sheet A9.3.0; Door Schedule: Please verify all doors located in this submittal (as indicated on Sheet A2.1.0) are included in the Door Schedule. 6. General: Please provide written responses to all review comments. |
04/27/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
05/08/2018 | TWEIDEM1 | APPROVAL SHELF | Completed |
05/08/2018 | TWEIDEM1 | OUT TO CUSTOMER | Completed |
05/08/2018 | TWEIDEM1 | REJECT SHELF | Completed |