Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM02113
Parcel: 140280260

Address:
2054 E GINTER RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM02113
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2018 MARTIN BROWN FIRE REVIEW Approved
05/31/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. As per the previous electrical plan review comment #6. It was requested to provide for AC disconnecting means within site and no more than 50' from the inverter per art 690.14D NEC. There is still no compliance. See definitions for "within site of" NEC.
#2. As per the previous electrical plan review comment #8. Provide a response.
Ref; 2012 IBC sec 107.2.1, 2012 NEC art 690.