Review Date Reviewer's Name Type of Review Description Status Comments
03/27/2018 JPEELDA1 FIRE REVIEW Reqs Change Provide parking lot details
04/18/2018 ERIC NEWCOMB ELECTRICAL-COMMERCIAL REVIEW Reqs Change 1. Specifications or documentation from service panel manufacturer that line-side tap will not void panel listing. NEC 110.3(B)
2. Provide specifications on electrical terminations, breakers and equipment for 90 degree rating on insulation. NEC 110.14(C)(1)
3 Provide a grounding detail for the panel racking system; submit panel racking installation specs. NEC 690.41
4. Provide clear, readible copies of equipment electrical data sheets; type is too small.
5. Provide a trench detail for the use of area and indicate depth. NEC 70-208
6. An AC disconnecting means shall be mounted within sight of the inverter(s). NEC 690.14
7. Provide specifications for mounting inverters; indicate location and height of inverter above walking surface. NEC 690.14
8. Provide inverter specifications for ungrounded system. NEC 690.35
9. Provide SE conductor size for verification of No. 4 AWG copper bond wire at combiner panel and SES. NEC TABLE 250.66
04/20/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/01/2018 BLARSON1 OUT TO CUSTOMER Completed