Permit Number: T18CM02109
Parcel: 140280230

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM02109
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2018 MARTIN BROWN FIRE REVIEW Approved
04/18/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide compliance with the Tucson/Pima County Outdoor Lighting Code. If claiming exemption per section 401.2.1(3), verify full cut-off shielding.
#2. Show the location of the branch circuit tap for the lighting and wiring methods for the luminaire branch wiring.
#3. Provide a grounding detail for the canopies and PV Modules.
#4. Provide a mounting detail for the inverters, AC Disconnects.
#5. Inverter cut sheets not legible. Print is to light.
Ref:2012 IBC sec 107.2.1, 2011 NEC
04/20/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
05/01/2018 BLARSON1 OUT TO CUSTOMER Completed