Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T18CM01977
Parcel: 12701005D

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM01977
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/15/2018 ANDREW CONNOR ZONING REVIEW Approved
03/15/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change Show the route, size, and termination of the condensate drain for the relocated computer room AC unit.
03/15/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/15/2018 ACONNOR1 ENGINEERING REVIEW Passed
03/15/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
03/15/2018 ROBERT SHERRY WATER REVIEW Completed
03/15/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
03/15/2018 JPEELDA1 FIRE REVIEW Approved
03/19/2018 BLARSON1 BUILDING-COMMERCIAL REVIEW Needs Review