Permit Number: T18CM01830
Parcel: 11451216D

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM01830
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/21/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Previous Comment 1; Sheet CV; Building Code: The IBC, IPC, IMC, IFC, and IECC all indicate the 2014 Edition. Please revise these per the first review comment.
2. Previous Comment 2; Sheet CV; Occupancy Allowance: Please revise the Building Code Edition to the 2012.
3. Previous Comment 17; Sheet A2.2; Demolition Keynotes: Note 4 is struck out, but now that note shows up on Elevation 1/A2.2. Please verify.
4. Sheet A4.1: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the Key Notes.
5. General: Please provide written responses to all review comments.
06/25/2018 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T18CM01830 - T.I. Renovation- Drive Through and Interior Remodel (Food Service Use)
Building Plan Review (1st Review) - McDonalds
30 S. Houghton Road

TRANSMITTAL DATE: June 25, 2018

DUE DATE: July 3, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

Previous Comments 2 and 3 still apply. As mentioned zoning, cannot approve the building plans until the PDSD Commercial Plans Reviewers have approved the plans.

2. PREVIOUS COMMENT: While the interior remodel and facade modifications do not affect any zoning requirements, prior to approval of the building plans by Zoning, the plans must be approved by all Commercial plans reviewers.

3. PREVIOUS COMMENT: Zoning will review the building plans on the next submittal to assure that the zoning comments have been addressed on the plans. Once all zoning comments have been addressed and the plans have been approved by all commercial plans reviewers zoning will also approve and stamp the plans.

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov

RESUBMITTAL OF THE FOLLOWING IS REQUIRED: building plans
06/28/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. As per the previous plan review comment #1, #2, #3.
The Parking lot lighting on the electrical site plan were not identified. If these luminaires are within this parcel please identify them and include them in the lumen calcs. If they are already in the lumen calcs then identify them as parking lot pole lighting. Verify they are in compliance for shielding, lumens output, color temperature output. Section 102.4.2, 104.2(1), (2), 104.2.1, 402.1
#2. The lamp source color temperature was not included for the canopy, parking, and rooftop luminaires.
#3. Provide for a special inspection for outdoor lighting as required per section 104.2.2, 106.2
#4. Identify the type and location of the 12 existing site fixtures shown in the lumen calcs.
Ref; 2012IBC sec 107.2.1, 2011 NEC, Tucson/Pima County Outdoor Lighting Code
Dan.santacruz@tucsonaz.gov