Permit Number: T18CM01816
Parcel: 132130860

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM01816
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/12/2018 JPEELDA1 FIRE REVIEW Approved
03/27/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide tempered water for the public restroom lavatories using approved devices conforming to ASSE 1070. Reference: Sections 416.5 and 607.1.2, IPC 2012.
2. Provide an automatic faucet for the lavatory, dispensing a maximum of 0.25 gallons per metering cycle. Verify that the automatic faucet will operate for a minimum time of 10-seconds. Reference: Section 416.6, IPC 2012, as amended by the City of Tucson and Section 606.4, ICC/ANSI A117.1-09.
3. Clarify the water sizing calculations. The calculations refer to what sounds like a booster pump: where is the pump located.
4. Provide pressure-absorbing devices for water lines equipped with quick acting or solenoid valves. The pressure-absorbing devices shall conform to ASSE 1010. Reference: Section 604.9, IPC 2012.
5. Appliances (e.g. ice makers) to be directly connected to the water supply system that do not have listed, integral backflow preventers or integral air gaps conforming to Section 608.13.1, IPC 2012 require backflow prevention. Specify the type of backflow prevention device required for each water connection. Reference: Sections 608.1 and 608.3, IPC 2012.
03/27/2018 ROBERT SHERRY WATER REVIEW Completed
03/28/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
03/29/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
04/09/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
04/09/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.0: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise the exit analysis plan verbiage.
2. Sheet A2.1; Floor Plan: The water heater (Keynote 4) and the mop sink (Keynote 5) are reversed in the Janitor's Room 110. Please revise.
3. Sheet A4.2; Elevation 3: Please indicate on the Elevation the required length of the accessible portion of the counter so that it meets the requirement of the ICC/ANSI Section 904.3.1.
4. General: Please provide written responses to all review comments.
04/09/2018 ERIC NEWCOMB ADA REVIEW Passed