Permit Review Detail
Review Status: Completed
Review Details: WALK THRU - COMM
Permit Number - T18CM01795
Review Name: WALK THRU - COMM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/12/2018 | MGAYOSS1 | ZONING | REVIEW | Passed | |
| 03/12/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. The feeders shown for the 200 amp panels are undersized. #2. Indicate conduit, conductor sizes and types for the panel 'C' feeders. #3. Indicate loads served for panel 'C'. Are they new or existing? If new, provide a complete panel schedule and indicate new panel 'C' on the plan. #4. Provide for a grounding electrode system for the maintenance building NEC art. 250.32A Ref 2012 IBC sec 107.2.1, 2011 NEC |