Permit Number: T18CM01795
Parcel: 12214013A

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T18CM01795
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/12/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. The feeders shown for the 200 amp panels are undersized.
#2. Indicate conduit, conductor sizes and types for the panel 'C' feeders.
#3. Indicate loads served for panel 'C'. Are they new or existing? If new, provide a complete panel schedule and indicate new panel 'C' on the plan.
#4. Provide for a grounding electrode system for the maintenance building NEC art. 250.32A
Ref 2012 IBC sec 107.2.1, 2011 NEC
03/12/2018 MGAYOSS1 ZONING REVIEW Passed