Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM01698
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/25/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Supply the site plans 2. Specify the minimum and maximum cycle times for the lavatories. Minimum 10-seconds, maximum 0.25 Gallon |
| 07/06/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 07/06/2018 | QJONES1 | ZONING | REVIEW | Needs Review | |
| 07/06/2018 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 07/06/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 07/06/2018 | QJONES1 | ENGINEERING | REVIEW | Needs Review | |
| 07/06/2018 | GPERU1 | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. The foundation plan in the structural calculation packet shows additional footings that are not shown on the foundation plan on sheet S1.0; please coordingate the structural calculation with the structural sheet. 2. Provide details for new footings on the structural sheet foundation plan. 3. Provide stair and handrail details for new stairs for loft. 4. Specify truss package for deferred submittals. |
| 07/06/2018 | QJONES1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 07/06/2018 | QJONES1 | APPROVAL SHELF | Completed |
| 07/06/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
| 07/06/2018 | QJONES1 | REJECT SHELF | Completed |