Permit Number: T18CM01698
Parcel: 129121500

Address:
1025 E 30TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM01698
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/05/2018 STEVE SHIELDS ZONING REVIEW Needs Review
03/05/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide COMcheck analysis for the addition to the building envelope, interior lighting, and for the new mechanical equipment,
2. Provide heating/ cooling calculations for the new HVAC units.
3. Provide ventilation calculations for the addition and for the changes to the church mezzanine.
4.Provide an exhaust fan for the mezzanine restroom.
5. Show how the air for the mezzanine returns to the HVAC unit.
6. Show how the exhaust fans are controlled.
03/05/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. #1.Please show controls, and branch circuit wiring for the three new exhaust fans. Designated circuit and panel.
#2. Locate the new AC unit and Insta Hot, disconnecting means, Circuit and panel desinations on the floorplans.
#3. Provide full compliance with the Tucson/Pima County Outdoor Lighting Code for the new exterior luminaires.
#4. Provide compliance with the 2012 IECC for lighting.
#5. Identify all luminaires with a mark on the floor plan that correlates with the luminaire schedule.
Ref: 2012 IBC sec 107.2.1, 2011 NEC art. 408.
03/05/2018 SSHIELD1 ENGINEERING REVIEW Needs Review
03/05/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Supply the site plans
2. Provide a specification for the mezzanine lavatory.
3. Verify the model number of the proposed water heater. Is the unit listed for outdoor use?
4. Provide cleanouts at the junctions of the building drains and the building sewers.
5. Where are the drinking fountains?
03/05/2018 ROBERT SHERRY WATER REVIEW Completed
04/25/2018 LPEREZ2 BUILDING-COMMERCIAL REVIEW Denied
04/25/2018 LPEREZ2 FIRE REVIEW Needs Review
04/25/2018 LPEREZ2 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review