Permit Number: T18CM01662
Parcel: 11460019B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM01662
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/03/2018 MCASTRO2 ZONING REVIEW Approved
04/03/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide heating/cooling load calculations that justify the capacity of the proposed AC unit. Reference: Section C403.2, IECC 2012.
2. Provide thermostatic control for the new AC unit that complies with the requirements of Section C403.2.4.1, C403.2.4.2, and C403.2.4.3, IECC.
3. Provide ventilation calculations per Section 403.3, IMC 2012.
04/03/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comment.
#1. Provide full compliance for the 2012 IECC for the lighting.
#2. Provide the expiration date for the seal on the electrical plans.
04/03/2018 MCASTRO2 ENGINEERING REVIEW Passed
04/03/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.1; Demolition Keyed Notes: Notes 3, 4, and 8 were not located on the plan. Please verify.
2. Sheet A1.1; Floor Plan: Per the IBC Section 1015.1(2), with a single exit, the common path of egress travel can not exceed the value in Table 1014.3 (75'). Please indicate on the plan that distance from the toilet room to the entrance is not exceeded. Measure the distance per the IBC Section 1016.3.
3. Sheet A1.2; Details 6, 7, 8, and 12: Please indicate the size and quantity of connectors at all metal stud framing (or indicate in the Specifications).
4. General: Please provide written responses to all review comments.
04/03/2018 ROBERT SHERRY WATER REVIEW Completed
04/03/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
04/03/2018 MARTIN BROWN FIRE REVIEW Approved
04/03/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed