Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM01610
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
04/10/2018 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Principle Planner PROJECT: La Suprema Apartments - TI T18CM01610 Building Plan (1st Review) TRANSMITTAL DATE: April 3, 2018 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. Until the building plans are stamped and approved by Historic Review Zoning cannot approve the building Plans 3. Until the above comments have been addressed and all other PDSD review agencies have approved the building plans zoning cannot approve. Once the above comment is addressed Zoning will provide an over the counter review. Call or email to schedule an appointment for this review. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
04/10/2018 | LOREN MAKUS | ENGINEERING | REVIEW | Passed | |
04/10/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A-0; Code Review (Separation Walls): Please indicate on the drawing that the separation walls (fire partitions) may have a fire resistance rating of 1/2 hour if the automatic sprinkler system meets the requirements of the IBC Section 903.3.1.1 (NFPA 13 sprinkler system). 2. Sheet A-0; Code Review (Corridor Fire Rating): Please indicate on the drawing the fire resistance rating of 1/2 hour applies if the automatic sprinkler system meets the requirements of the IBC Section 903.3.1.1 (NFPA 13 sprinkler system). 3. Sheet A-0; Code Review (Automatic Sprinklers): Please indicate on the drawings the automatic sprinkler system must meet the requirements of the IBC Section 903.3.1.1 (NFPA 13 sprinkler system). 4. Sheet A-0; Code Review: Please add a note to the drawings indicating openings in 1/2 hour fire resistant rated walls shall meet the requirements of the IBC Table 716.5 (1/3 hour rated doors). 5. Sheet A-0; Code Review (Emergency Escape): Please indicate on the drawings the minimum size of the opening (Section 1029.2), minimum dimensions of the opening (1029.2.1), maximum height of the opening from the floor (1029.3), and operational constraints (1029.4). 6. Sheet A-0; Accessibility Code Compliance: Please include with the Type "B" units a reference to the ICC/ANSI Section 1004. 7. Sheet A-1; Demolition Plan: In Note 11, please add that the general contractor shall notify the architect if an existing footing is in an alternate location or the condition of the existing footing should be investigated. 8. Sheet A-2; Wall Key: Please indicate on the drawings the fire resistance rating and the Item Number (per the IBC Table 721.1) of the existing walls in the Wall Key. 9. Sheet A-2; Window Schedule: Please add to the "Notes" that the general contractor shall notify the architect if an existing lintel is damaged or missing. 10. Sheet A-4; Detail 6: Where the new 2 x 8 joists overlap the existing joists, please indicate on the detail the length of the lap required, and the size and quantity of connectors at each new joist. 11. General: Please provide written responses to all review comments. |
04/10/2018 | JPEELDA1 | FIRE | REVIEW | Approved | |
04/12/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please provide a complete grounding detail for the new electrical service. Ref: 2011 NEC, 2012 IBC |
04/12/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
04/12/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. The minimum ventilation rate for private dwellings is the greater of 15 CFM per person (based on two persons per bedroom) or 0.35 air changes per hour. Reference: Section 403.3, IMC 2012. 2. Mechanical exhaust is required from kitchens in private dwelling units at a rate of 100 CFM (intermittent) or 25 CFM (operating continuously while the space is occupied). Reference: Section 403.3, IMC 2012. 3. Provide ventilation for the common entry and other corridors. Reference: Section 403.3, IMC 2012. 4. Provide a REScheck or COMcheck analysis of the alterations to the existing building envelope. Reference: Sections R101.5, R101.4.2, R101.4.5, and R103.2, IECC 2012. |
04/12/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Provide third-party listing and material standards for all plumbing fixtures specified or provided by others. Reference: Sections 303.4 and 402, IPC 2012. 2. Central laundry rooms containing automatic clothes washers in multi-family dwellings shall have a floor drain to drain the entire floor area. The minimum drain outlet is 3". Reference: Section 412.4, IPC 2012. 3. An approved 2-way cleanout fitting is a single fitting, not a field-assembled group of individual fittings as shown in detail 203. Cleanouts also shall open to allow cleaning in the direction of flow. Clarify how detail 203 complies with these requirements. Reference: Sections 708.3.5 and 708.5, IPC 2012. 4. Indirect waste receptors (e.g. shall not be installed in a closet or an unventilated space. Reference: Section 802.3, IPC 2012. |
04/20/2018 | ERIC NEWCOMB | ADA | REVIEW | Passed |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
04/20/2018 | FERNE RODRIGUEZ | REJECT SHELF | Completed |