Permit Number: T18CM01575
Parcel: 13013069A

Address:
3525 E 34TH ST

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T18CM01575
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide complete compliance with the TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE. See section 104.2 for Plan and Permit Submittal Requirements, and resubmit with all the information on the plans as outlined in this section. The OLC can be printed or downloaded from www.tucsonaz.gov/pdsd.
#2. Ref: Plan Sheet E0.0, E2.0. The color temperature output shown on the luminaire schedule does not correlate with the 'FIXTURE S1B MOUNTING DETAIL.
'Ref; 2012 IBC sec 107.2.1, 2011 NEC, Tucson/Pima County Outdoor Lighting Code.
03/09/2018 QJONES1 BUILDING-COMMERCIAL REVIEW Needs Review
03/09/2018 QJONES1 ZONING REVIEW Needs Review