| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/28/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide complete compliance with the TUCSON/PIMA COUNTY OUTDOOR LIGHTING CODE. See section 104.2 for Plan and Permit Submittal Requirements, and resubmit with all the information on the plans as outlined in this section. The OLC can be printed or downloaded from www.tucsonaz.gov/pdsd. #2. Ref: Plan Sheet E0.0, E2.0. The color temperature output shown on the luminaire schedule does not correlate with the 'FIXTURE S1B MOUNTING DETAIL. 'Ref; 2012 IBC sec 107.2.1, 2011 NEC, Tucson/Pima County Outdoor Lighting Code. |