Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM01571
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/28/2018 | ALEXANDRA HINES | ZONING | REVIEW | Approved | |
| 02/28/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 02/28/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/28/2018 | AHINES2 | ENGINEERING | REVIEW | Passed | |
| 02/28/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Needs Review | |
| 02/28/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 03/02/2018 | JVINCEN1 | FIRE | REVIEW | Approved | |
| 03/06/2018 | CLAYTON TREVILLYAN | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 03/06/2018 | CTREVIL1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |