Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM01535
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/27/2018 | MMORENO1 | ZONING | REVIEW | Approved | |
| 03/27/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 03/27/2018 | ERIC NEWCOMB | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 03/27/2018 | MMORENO1 | ENGINEERING | REVIEW | Passed | |
| 03/27/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 03/27/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 03/27/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 03/27/2018 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 03/27/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |