Permit Review Detail
Review Status: Completed
Review Details: RESIDENTIAL - BLDG/WWM
Permit Number - T18CM01525
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/28/2018 | CLAYTON TREVILLYAN | BUILDING-RESIDENTIAL | REVIEW | Reqs Change | T18CM01525 Page 3 - Detail 5 is the wrong application for the footing indicated near the existing kitchen. Page 3 - Identify the detail necessary for the patio turn down condition located in the southwest corner of the building. Page 3, 5 - Identify interior load bearing conditions for three-point bearing trusses or indicate the appropriate connection detail for non-load bearing truss conditions at interior walls. Page 6 - Provide an accurate detail for the roof cricket condition at intersecting roof lines. Page 6, 8 - Identify the size of carport rafters. Page 6, 8 - Identify flashing at roof to wall intersections. Page 8 - Provide the correct detail reference above the new bathroom. Page 9 - Provide consistent HVAC equipment selection data between Manual J calculations, mechanical layout, and electrical layout sheets. Page 10 - Provide a minimum ¾" water meter for the proposed water demand. Page 11 - Identify the location and type of proposed unshielded exterior lighting. Page 11 - Clarify all overprinted circuit designations at kitchen and bathroom receptacles. Page 11 - Identify circuit designations at peninsula receptacles. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 04/03/2018 | QJONES1 | APPROVAL SHELF | Completed |
| 04/03/2018 | QJONES1 | OUT TO CUSTOMER | Completed |
| 04/03/2018 | QJONES1 | REJECT SHELF | Completed |