Permit Number: T18CM01447
Parcel: 11205001A

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T18CM01447
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/27/2018 ANDREW CONNOR ZONING REVIEW Approved
03/21/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
03/21/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet PV1.1 (Canopy Profile); Sheet S2.0 (Frame Elevation): The Sheet S2.0 Elevation indicates a 12'-6" dimension (at the high end) from grade to a point on the beam, while the Sheet PV1.1 Profile indicates a 12'-6" dimension (approximate) from grade to the top of the solar panel. Please coordinate.
2. Sheet S2.0 (Roof Framing Plan); Structural Calculations (Sheet 13): The calculations indicate 1000S250-68 purlins while the Framing Plan indicates (2)800S350-68 purlins. Sheets 14 through 17 of the calculations indicate the 800S350-68 purlins. Please coordinate.
3. Sheet S3.0 (Detail 202); Structural Calculations (Sheets 24 through 27): The calculations indicate a moment end plate connection of the beam to the column, while the detail indicates the beam bearing on top of the column. Please coordinate.
4. General: Please provide written responses to all review comments.

Final Status