Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM01395
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/22/2018 | LPEREZ2 | ZONING | REVIEW | Needs Review | |
| 02/22/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | 1. Clarify the ventilation calculations. Natural ventilation is not appropriate with the exhaust requirements in the suite. Correct the arithmetic on the OSA ventilation table and show that the three heat pumps supply the required amount of outside air. 2. Show that the cooling and heating load calculations are based on the exterior conditions noted in the IECC as amended by the City of Tucson. 3. Coordinate the heat pump unit schedule with the mechanical design (i.e. two existing heat pumps and one new heat pump). 4. Show the size, route, and termination of the condensate drains for the three heat pumps. |
| 02/22/2018 | LPEREZ2 | ELECTRICAL-COMMERCIAL | REVIEW | Needs Review | |
| 02/22/2018 | LPEREZ2 | ENGINEERING | REVIEW | Needs Review | |
| 02/22/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 02/22/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 02/22/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Reqs Change | 1. Plumbing vents shall rise at least 6" aqbove the flood rim of the fixture they serve prior to running horizontally (e.g. the flow control device for the grease trap). 2. 2-way cleanouts may only be used at the junction of the building drain & the building sewer. 3. Hand sinks connected to sanitary waste shall be labeled per Section 1003, IPC 2012 as amended by the City of Tucson. 4. Provide a vent downstream of the grease interceptor. |
| 02/22/2018 | JPEELDA1 | FIRE | REVIEW | Approved | |
| 02/22/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |