Review Date Reviewer's Name Type of Review Description Status Comments
02/22/2018 LPEREZ2 ZONING REVIEW Needs Review
02/22/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Clarify the ventilation calculations. Natural ventilation is not appropriate with the exhaust requirements in the suite. Correct the arithmetic on the OSA ventilation table and show that the three heat pumps supply the required amount of outside air.
2. Show that the cooling and heating load calculations are based on the exterior conditions noted in the IECC as amended by the City of Tucson.
3. Coordinate the heat pump unit schedule with the mechanical design (i.e. two existing heat pumps and one new heat pump).
4. Show the size, route, and termination of the condensate drains for the three heat pumps.
02/22/2018 LPEREZ2 ELECTRICAL-COMMERCIAL REVIEW Needs Review
02/22/2018 LPEREZ2 ENGINEERING REVIEW Needs Review
02/22/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Needs Review
02/22/2018 ROBERT SHERRY WATER REVIEW Completed
02/22/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Plumbing vents shall rise at least 6" aqbove the flood rim of the fixture they serve prior to running horizontally (e.g. the flow control device for the grease trap).
2. 2-way cleanouts may only be used at the junction of the building drain & the building sewer.
3. Hand sinks connected to sanitary waste shall be labeled per Section 1003, IPC 2012 as amended by the City of Tucson.
4. Provide a vent downstream of the grease interceptor.
02/22/2018 JPEELDA1 FIRE REVIEW Approved
02/22/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed