Permit Number: T18CM01386
Parcel: 137055230

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM01386
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/05/2018 JPEELDA1 FIRE REVIEW Approved
03/20/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Completed
03/20/2018 ROBERT SHERRY WATER REVIEW Completed
03/20/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide calculations to show that the revised ventilation system for the retail sales floor provides outside air in accordance with Section 403.3, IMC 2012.
2. Provide heating and cooling load calculations that justify the capacities of the heating and cooling equipment specified for the project. Reference: Section 6.4.2.1, ASHRAE 90.1-2010.
03/21/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A111; Section 4: Please indicate the horizontal length and vertical length of the 1/4" bent steel plate.
2. Sheet A111; Section 5: Please indicate the minimum embedment length of the wedge anchors, or indicate the anchor length.
3. Sheet A111; Detail 2: Please darken all dimensions and revise those dimension heights to a minimum 3/32".
4. Sheet A111; Floor Plan: The City of Tucson requires all lettering (upper and lower case) to be a minimum of 3/32" in height. Please revise.
5. Sheet A125; Blocking Keynote 8: This note references Detail 5/A701. Please verify that reference.
6. Sheet A601; Interior Partitions: Is a note or reference made on this sheet for the typical partition stud spacing? A note at the restroom walls indicates 16" OC, and the specifications reference the drawings. Please verify and provide as required.
7. Sheet S111; Elevation 4: Please provide structural calculations for the new tube column, base plate, and anchor bolts at the trucker's door.
8. Structural Calculations; Code Search: The occupancy group is listed as B Business. Please revise.
9. General: Please provide written responses to all review comments.
03/21/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please provide full compliance with the Tucson/Pima County Outdoor Lighting Code for the exterior lighting. This Code can be printed or downloaded from, www.tucsoaz.gov/pdsd.