Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM01332
Parcel: 125076370

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM01332
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2018 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
02/21/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Completed
02/21/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/21/2018 ROBERT SHERRY WATER REVIEW Completed
02/21/2018 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Reqs Change 1. Sheet A1.0; Keynote 7: Per the ICC/ANSI Section 904.3.1, the service counter must be 36" minimum in length and 36" maximum in height. Please revise the keynote.
2. Sheet A4.0; Detail 4: Please provide the horizontal angles (top and bottom) size and connection to the blocking. Please coordinate this detail with Detail 1 on Sheet P2.0.
02/21/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change Coordinate the design of the water heater support with the architect
02/22/2018 MCASTRO2 ENGINEERING REVIEW Passed
02/22/2018 MCASTRO2 ZONING REVIEW Approved
02/22/2018 JPEELDA1 FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
02/26/2018 BLARSON1 OUT TO CUSTOMER Completed