Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM01329
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/21/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 02/21/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | Provide an exhaust duct for the proposed clothes dryer. Reference: section 504.6.6, IMC 2012. |
| 02/21/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Completed | |
| 02/21/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 02/21/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet A1.1; Wall Type Sections: Please indicate the size and gauge of the diagonal brace studs, the spacing of the brace studs (on Wall Type W2), and the size and quantity of the connectors of the brace studs to the top of the wall and to the structure above. |
| 02/22/2018 | MCASTRO2 | ENGINEERING | REVIEW | Passed | |
| 02/22/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/22/2018 | MCASTRO2 | ZONING | REVIEW | Approved | |
| 02/23/2018 | JVINCEN1 | FIRE | REVIEW | Approved |