Permit Number: T18CM01325
Parcel: 11706320C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T18CM01325
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/28/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change 1. Provide an exhaust duct for the proposed clothes dryer. Reference: Section 504.6.6, IMC 2012.
2. Clarify detail 101. Why is a duct located below the fan housing for a side-discharge supply fan?
3. Provide the specifications for the glycol chiller, including the leaving fluid temperature. Reference: Section C403.2.3.2, IECC 2012.
4. Verify that the size of the combustion air ducts (shown as two openings with vertical ducts) complies with the requirements of Section 304.6.1, IFGC 2012.
02/28/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Reqs Change 1. Provide the capacity of the proposed propane tank and the required clearances from the building and building components. Reference: Section 401.2, IFGC 2012 (NFPA 58).
2. Clarify the size of the two horizontal branches for the three lavatories; on sheet P1, they are 4" connecting to a 3" horizontal branch but in diagram A/P3, one is 2" and the other has no dimension. Reference: Section 706.2, IPC 2012 and Section 107.2.1, IBC 2012.
3. Coordinate the equipment labels in the area of the tasting bar with the architect. Reference: Section 107.2.1, IBC 2012.
4. Identify the equipment (plumbing fixtures?) located on the east wall behind the tasting bar. Reference: Section 107.2.1, IBC 2012.