Review Date Reviewer's Name Type of Review Description Status Comments
02/27/2018 JPEELDA1 FIRE REVIEW Approved
03/14/2018 PIMA COUNTY BUILDING-COMMERCIAL REVIEW Reqs Change T18CM01321 – PLAN REVIEW COMMENTS
Reviewer: Charlie Bard, March 12, 2018
BUILDING – COMMERCIAL
Per the basement level plan and the ground level plan the south stair is unenclosed and terminates in the ground floor lobby. Also, per the ground level plan the south exit stair from the upper floors is an interior stair and also terminates in the ground level lobby. Although 2012 IBC 1009.3 exception 1 allows an exit access stair between two stories to be unenclosed, 1027.1 exception 1 (1.2) does not allow this between the basement and ground floor in this instance. Per 1027.1 the entire area of the level of exit discharge shall be separated from areas below by construction with the same fire-resistance rating of the stair enclosure to floors above, which is 1-hour. Provide a 1-hour enclosure for this stairway either on the basement level or the ground floor level.
Per 2012 IBC 1027.1 exception 1(1.1) the building main exit/entry door in the lobby must be readily visible and identifiable from the point of termination of the exit stair enclosure. In the current configuration the exit door is not visible to an occupant passing through the door from the stair enclosure. The Bikes storage room wall is in the line of sight.
Provide exit egress calculation for the worst case to show you meet require travel distance. Show on plans.
03/14/2018 PIMA COUNTY MECHANICAL-COMMERCIAL REVIEW Reqs Change MECHANCIAL PLUMBING AND ELECTRICAL
Mechanical, Plumbing and E-2 plans are all marked not for construction.
Provide cut sheets for lighting fixture include outdoor lighting fixtures.
03/14/2018 PIMA COUNTY ELECTRICAL-COMMERCIAL REVIEW Reqs Change MECHANCIAL PLUMBING AND ELECTRICAL
Mechanical, Plumbing and E-2 plans are all marked not for construction.
Provide cut sheets for lighting fixture include outdoor lighting fixtures.
03/14/2018 FRODRIG2 WATER REVIEW Approved
03/14/2018 PIMA COUNTY PLUMBING-COMMERCIAL REVIEW Reqs Change MECHANCIAL PLUMBING AND ELECTRICAL
Mechanical, Plumbing and E-2 plans are all marked not for construction.
Provide cut sheets for lighting fixture include outdoor lighting fixtures.
03/22/2018 DAVID RIVERA ZONING REVIEW Reqs Change FROM: David Rivera
PDSD Zoning Review Section

PROJECT: T18CM01321 - The Westerner T.I. (Not for C of O approval by zoning)
Building Plans (1st Review)
10 E Broadway Boulevard

TRANSMITTAL DATE: March 22, 2018

DUE DATE: March 22, 2018

COMMENTS: Please resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.


1. COMMENT: Zoning has reviewed the building plans but cannot approve them at this time. The proposed modifications to the interior do not affect any zoning requirements and the use of the building and site is not changing.

2. COMMENT: In addition, the building plans must be approved by the PDSD or 3rd Party commercial plans reviewers before zoning can approve the plans.


3. COMMENT: Once the plans have been approved by all Commercial Plans reviewers and no site changes are made that affect zoning requirements, zoning will stamp and sign the building plans as it pertains to the zoning review purview.

4. COMMENT: Clarify if the use is specifically for future Administrative Office use only?

If you have any questions about this transmittal, Contact David Rivera on Tuesday or Wednesday at (520) 837-4957 or by email at David.Rivera@tucsonaz.gov or contact Steve Shields, (520) 837-4956 or Steve.Shields@tucsonaz.gov
03/28/2018 ALEXANDRA HINES DESIGN PROFESSIONAL REVIEW Needs Review