Permit Number: T18CM01222
Parcel: 12604266B

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T18CM01222
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
#1. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code. Can be printed or downloaded from www.tucsonaz.gov/pdsd. See section 104 for permit and plan submittal.
#2 Provide a complete site plan and electrical plan for the new lighting installation. Plans must be sealed by a registered Engineer registered in the State of Arizona.
Ref: 2012 IBC sec 107.2.1, 2011 NEC, City of Tucson Commercial plan Submittal Requirements.
02/16/2018 MCASTRO2 ZONING REVIEW Passed