Permit Number: T18CM01221
Parcel: 13705494H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T18CM01221
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/16/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved
02/16/2018 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Reqs Change The specified heat pumps have an HSPF that does not meet the requirements of Section C406.2, IECC 2012. The submitted COMcheck mechanical compliance shows an HSPF of 8.5 but the unit has an HSPF of 8.0.
02/16/2018 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
02/16/2018 ROBERT SHERRY WATER REVIEW Completed
02/21/2018 KROBLES1 ZONING REVIEW Needs Review
02/21/2018 KROBLES1 ENGINEERING REVIEW Needs Review
02/21/2018 KROBLES1 BUILDING-COMMERCIAL REVIEW Needs Review
02/21/2018 KROBLES1 FIRE REVIEW Needs Review
02/21/2018 KROBLES1 COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review