Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM01221
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/16/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 02/16/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Reqs Change | The specified heat pumps have an HSPF that does not meet the requirements of Section C406.2, IECC 2012. The submitted COMcheck mechanical compliance shows an HSPF of 8.5 but the unit has an HSPF of 8.0. |
| 02/16/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 02/16/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 02/21/2018 | KROBLES1 | ZONING | REVIEW | Needs Review | |
| 02/21/2018 | KROBLES1 | ENGINEERING | REVIEW | Needs Review | |
| 02/21/2018 | KROBLES1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 02/21/2018 | KROBLES1 | FIRE | REVIEW | Needs Review | |
| 02/21/2018 | KROBLES1 | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review |