07/25/2018 GPERU1 BUILDING-COMMERCIAL REVIEW Denied 1. All architectural sheets require seal by the professional registrant; sheets C-001, C-111, D2.0, S2.0, A1.0, A1.1, A2.0, A4.0, A5.0.
2. Provide written response to previous architectural and structural comments.
3. Previous Comment 3; Sheet S1.0; Structural Calculations: Please provide the structural calculations for the foundation/footings. The two submitted sets have framing design calculations, but no footing/foundation design calculations were included.
4. The structural calculations are required to be sealed by the engineer of record.
07/25/2018 MARTIN BROWN FIRE REVIEW Reqs Change Per response letter. Sprinkler contractors typically do not install fire alarm systems. Add fire alarm to list of deferred submittals on sheet A0.0.
Unable to determine from hardware set 10 if Von Duprin 2670 Guard-X 325TB is panic hardware. Please clarify. FYI, section 907.2.1 of the International Fire Code references fire alarms, not panic hardware. panic hardware.
07/25/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved