Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T18CM01215
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/19/2018 | MARTIN BROWN | FIRE | REVIEW | Reqs Change | Unable to determine if door 102 on sheet A1.0 has panic hardware. Please confirm. Per section 907.2.1 of the 2012 International Fire Code, a fire alarm system is required in A occupancies with an occupant load of 300 or greater. Please indicate a deferred submittal for fire alarms. Please clarify if the fan shown on Sheet E1.0 (F14) is a High Volume Low Speed type. If it is, please add note indicating sprinkler water flow will shut power to fan. |
| 04/27/2018 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 04/27/2018 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Completed | |
| 04/27/2018 | ROBERT SHERRY | WATER | REVIEW | Completed | |
| 05/01/2018 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Reqs Change | 1. Sheet COV; Project Summary: There is no information included in the project summary. Please provide. 2. Sheet D2.0; Keynotes: It appears notes 12 and 13 have been reversed. Please verify. 3. Sheet S1.0; Foundation Design: A note indicates the foundations have been designed for an assumed soil bearing pressure of 2000 psf. Per the IBC Table 1806.2 and City of Tucson requirements, when the bottom of the footing is a minimum of 18" below lowest grade or finish floor (whichever is lower), an allowable soil bearing pressure of 1500 psf may be used. Please include the IBC reference (Section 1806) and the allowable soil bearing value on the drawings. Revise the foundation calculations as required. 4. Sheet S1.0; Roof Framing Keynotes: Please add a detail on the drawings for the extension of the existing wall (note 15). 5. Sheet S1.0; Foundation Keynotes: At note H, please add to field verify those dimensions. 6. Sheet A2.0; Exit Travel Distance: Please add a note that references the IBC Section 1018.4 for allowable dead end distances in corridors. Verify this project meets those requirements. 7. Sheet A5.0; Detail 4: Where is this detail cut on a plan or referenced in a note? There is no new steel beam on this project. Please verify. 8. Sheet A5.0; Detail 5: Where is this detail cut on a plan or referenced in a note? Please verify. 9. General: Please provide two sets of structural calculations for this project. 10. General: Please provide written responses to all review comments. |
| 05/03/2018 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 05/07/2018 | STEVE SHIELDS | ZONING | REVIEW | Reqs Change | PDSD TRANSMITTAL FROM: Steve Shields Principle Planner PROJECT: 968 W. Irvington Road T18CM01215 Building Plan (1st Review) TRANSMITTAL DATE: May 7, 2018 1. The building plans have been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed. 2. The civil sheets provided in the building set either need to be the approved Development Package DP18-0077, marked as for reference only or removed from the building set. 3. Until all other PDSD review agencies have approved the building plans zoning cannot approve. Once the above comments are addressed Zoning will provide an over-the-counter review. Please call or email to schedule an appointment for this review. If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956 |
| 05/10/2018 | DAN SANTA CRUZ | ELECTRICAL-COMMERCIAL | REVIEW | Reqs Change | Please address the following electrical plan review comments. Also provide a written response. #1. Provide complete compliance with the Tucson/Pima County Outdoor Lighting Code for the exterior lighting. This Code can be printed or downloaded from www.tucsonaz.gov/pdsd. See section 104 for plan submittal requirements. |
| 05/14/2018 | JOHN VAN WINKLE | ENGINEERING | REVIEW | Reqs Change | T18CM01215 1: Sheet C-001. Detail 12, update ground clearance from grade to lower sign to be 7' 2: The civil sheets provided in the building set either need to be the approved Development Package DP18-0077, marked as for reference only or removed from the building set John Van Winkle, P.E. john.vanwinkle@tucsonaz.gov 520-837-5007 |