Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T18CM01185
Parcel: 134263900

Address:
804 S LANGLEY AV

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T18CM01185
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/21/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Approved