Permit Number: T18CM01185
Parcel: 134263900

Address:
804 S LANGLEY AV

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T18CM01185
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/15/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Provide a one line diagram from the service equipment to the new sub panel to verify capacities are sufficient to handle the increased load. Also provide accurate load calcs.
Ref: 2012 IBC 107.2.1, 2011 NEC 220.