Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T18CM01184
Parcel: 134263540

Review Status: Completed

Review Details: WALK THRU - COMM

Permit Number - T18CM01184
Review Name: WALK THRU - COMM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/15/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Provide a one line diagram from the service equipment to the new sub panel to verify capacities are sufficient to handle the increased load. Also provide accurate load calcs.
Ref: 2012 IBC 107.2.1, 2011 NEC 220.