Permit Number: T18CM01145
Parcel: 30503004B

Review Status: Completed

Review Details: REVISION - - 1ST

Permit Number - T18CM01145
Review Name: REVISION - - 1ST
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/08/2018 LPEREZ2 BUILDING-COMMERCIAL REVIEW Needs Review
05/08/2018 DAN SANTA CRUZ ELECTRICAL-COMMERCIAL REVIEW Reqs Change Please address the following electrical plan review comments. Also provide a written response.
31. Plan Sheet E1.0 not sealed by Registrant.
#2. Provide shielding information for the proposed new luminaires.
#3. Identify the 30 KVA transformer on plan sheet E3.0.
#4. Indicate if the receptacles are GFI protected.
Ref: 2012 IBC Sec 107.2.1, 2011 NEC

Final Status

Task End Date Reviewer's Name Type of Review Description
05/08/2018 LPEREZ2 OUT TO CUSTOMER Completed